5.1 Requirements for Parts of Buildings
5.1.1 Plinth
5.1.1.1 The plinth or any part of a building or outhouse shall be so located with respect to the surrounding ground level that adequate drainage of the site is assured. The height of the plinth shall be not less than 450 mm from the surrounding ground level, in case of independent houses and not less than 300mm in case of other buildings.
5.1.1.2 Interior Courtyards and Covered Parking: Every interior courtyard shall be raised at least 150 mm above the determining ground level and shall be satisfactorily drained.
5.1.2 Habitable Rooms
5.1.2.1 Height
The clear height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab) provided that the minimum clear headway under any beam shall not be less than 2.4m In the case of pitched roof, the average height of rooms shall not be less than 2.75m. The minimum clear head room under a beam, folded plates or eaves shall be 2.4m. In the case of air-conditioned
rooms, a height of not less than 2.4mmeasured from the surface of the floor to the lowest point of air-conditioning duct or the false ceiling shall be provided.
5.1.2.2 The requirements of clause 5.1.2.1 shall apply to residential, business and mercantile buildings. For educational and industrial buildings, the following minimum requirements apply:
| Sl. No | Type of Occupancy | Ceiling height |
|---|---|---|
| 1 | Educational Buildings | Ceiling height 3.6m for all regions |
| 2 | Industrial Buildings | Ceiling height 3.6m, except when air-conditioned, 3m (Factory Act 1948 and Rules therein shall govern such heights, where applicable) |
5.1.2.3 Size
The area of habitable room shall not be less than 9.5Sq.m, where there is only one room with a minimum width of 2.4m. Where there are two rooms, one of these shall not be less than 9.5Sq.m and the other not less than 7.5Sq.m, with a minimum width of 2.1m.
5.1.3 Kitchen
5.1.3.1 Height
The height of a kitchen measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.75 m, except for the portion to accommodate floor trap of the upper floor.
5.1.3.2 Size
The area of a kitchen where separate dining area is provided shall be not less than 5.0 Sq. m with a minimum width of 1.8m. Where there is a separate store, the area of the kitchen may be reduced to 4.5Sq.m. A kitchen, which is intended for use as a dining area also, shall have a floor area of not less than 7.5 Sq. m with a minimum width of 2.1m.
5.1.3.3 Other Requirements
Every room to be used as kitchen shall have:
(a) Unless separately provided in a pantry, means for the washing of kitchen utensils which shall lead directly or through a sink to a grated and trapped connection to the waste pipe
(b) An impermeable floor
(c) A flue, if found necessary
5.1.4 Bathrooms and Water-Closets
5.1.4.1 Height
The height of a bathroom or water-closet measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.1m.
5.1.4.2 Size
The area of a bathroom shall not be less than 1.8Sq.m with a minimum width of 1.2m. The floor area of water-closet shall be 1.1Sq.m with a minimum width of 0.9m. If bath and watercloset are combined, its floor area shall not be less than 2.8Sq.m with a minimum width of 1.2m.
5.1.4.3 Other Requirements
Every bathroom or water-closet shall:
(a) Be so situated that at least one of its walls shall face a shaft or open space
(b) Not be directly over or under any room other than another water-closet, washing place, bath or terrace, unless it has a water-tight floor;
(c) Have the platform or seat made of water-tight non-absorbent material;
(d) be enclosed by walls or partitions and the surface of every such wall or partition shall be finished with a smooth impervious material to a height of not less than 1 m above the floor of such a room;
(e) Be provided with an impervious floor covering, sloping towards the drain with a suitable grade and not towards VERANDAH or any other room; and
(f) Have a window or ventilator, opening to a shaft or open space, of area not less than 0.3Sq.m with side not less than 0.3m.
5.1.4.4 No room containing water closets shall be used for any purpose except as a lavatory and no such room shall open directly into any kitchen or cooking space by a door, window or other opening. Every room containing water-closet shall have a door completely closing the entrance to it.
5.1.5 Loft
5.1.5.1 Height
The minimum head-room of loft shall be 2.2m.
5.1.5.2 Size
A loft in a habitable room shall not cover more than 25 percent of the area of the floor on which it is constructed and shall not interfere with the ventilation of the room under any circumstances.
5.1.6 Mezzanine Floor
5.1.6.1 Height
It shall have a minimum height of 2.2m.
5.1.6.2 Size
The minimum size of the mezzanine floor, if it is to be used as a living room, shall not be less than 9.5Sq.m. The aggregate area of such mezzanine floor in a building shall in no case exceed one third the plinth area of the building.
5.1.6.3 Other Requirements
A mezzanine floor may be permitted over a room or a compartment provided:
(a) it conforms to the standard of living rooms as regards lighting and ventilation in case the size of mezzanine floor is 9.5Sq.m or more
(b) It is so constructed as not to interfere under any circumstances with the ventilation of the space over and under it;
(c) Such mezzanine floor is not sub-divided into smaller compartments;
(d) Such mezzanine floor or any part of it shall not be used as a kitchen; and
(e) In no case shall a mezzanine floor be closed so as to make it liable to be converted into unventilated compartments.
5.1.7 Store Room
5.1.7.1 Height
The height of a store room shall be not less than 2.1m.
5.1.7.2 Size
The size of a store room, where provided in a residential building, shall be not less than 3 Sq.m
5.1.8 Garage
5.1.8.1 Height
The height of a garage shall be not less than 2.4m.
5.1.8.2 Size
The size of garages shall be as below:
(a) Private Garage - 3.0 m × 6.0 m, minimum; and
(b) Public Garage - Based on the number of vehicles parked by ECS
5.1.9 Basement
5.1.9.1 The Authority in accordance with the land use and other provisions specified under the Zonal Regulations shall allow the construction and usage of the basement
5.1.9.2 The basement shall have the following requirements:
(a) Every basement shall be in every part at least 2.4 m in height from the floor to the underside of the roof slab/beam joists and at any part shall not exceed 4.5m in height;
(b) Adequate ventilation shall be provided for the basement. The ventilation requirements shall be the same as required by the particular occupancy according to byelaws. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans, air-conditioning systems, etc.
(c) The maximum height at the top of the roof slab of the basement floor shall not be more than 1.2m above the average surrounding ground level;
(d) Adequate arrangements shall be made such that surface drainage does not enter the basement;
(e) The walls and floors of the basement shall be watertight and be so designed that the effects of the surrounding soil and moisture, if any, are taken into account in design and adequate damp proofing treatment is given; and
(f) The access to the basement shall be separate from the main and alternative staircase providing access and exit from higher floors.
(g) Where the staircase is continuous in the case of buildings served by more than one staircase, the same shall be of enclosed type serving as a fire separation from the basement floor and higher floors. Open ramps shall be permitted if they are constructed within the building line subject to the provision of (d). The exit requirements in basements shall comply with the provisions of these Byelaws.
5.1.10 Chimneys
The chimneys shall be built at least 0.9 m above flat roofs, provided the top of the chimneys is not below the top of the adjacent parapet wall. In the case of sloping roofs, the chimney top shall not be less than 0.6 m above the ridge of the roof in which the chimney penetrates.
5.1.11 Parapet
Parapet walls and handrails provided on the edges of roof terraces, balcony, verandah, etc. shall not be less than 1.0 m and not more than 1.2 m in height from the finished floor level.
(i) The above shall not apply where roof terrace is not accessible by a staircase.
(ii) However on terrace floor in the portion where installations like DG Set, Water Tank and other, screening parapet of a suitable height may be constructed to hide such equipment’s etc. and there is no need to have uniform increase in the height of the parapet.
5.1.12 Boundary Wall
The requirements of the boundary wall shall be as follows:
(a) Except with the special permission of the Authority, the maximum height of the compound wall shall be 1.5 m above the Centre line of the front street. Compound wall up to 2.4 m height may be permitted if the top 0.9 m is of open type construction of a design to be approved by the Authority.
(b) In the case of a corner plot, the boundary wall shall be constructed as specified by the ULB or the Government. and
(c) However, the provisions of (a) and (b) are not applicable to boundary walls of jails. In electric sub-stations, transformer stations, institutional buildings like sanatoria, hospitals, industrial buildings like workshops, factories and educational buildings like schools, colleges, including hostels and other uses of public utility undertakings and strategically sensitive buildings, a height up to 2.4 m may be permitted by the Authority.
5.1.13 Septic Tanks
Where a septic tank is used for sewage disposal, the location, design and construction of septic tank shall conform to requirements as notified by the Government.
5.1.14 Office-cum-Letter Box Room
In the case of multi-storeyed multi-family dwelling apartments constructed by existing and proposed Apartment Owners Associations, limited companies and proposed societies, an office-cum-letter box room of 10Sq.m shall be provided on the ground floor. In case the number of flats is more than 20, the minimum size of the office-cum-letter box room shall be 20Sq.m and shall not exceed 40Sq.m. If the area of the office-cum-letter box room exceeds 40Sq.m, the additional area shall be considered for FAR calculation.
In case of Business buildings provisions shall be made for letter boxes on the entrance floor as per the requirements of the postal department.
5.1.15 Meter Rooms
For all buildings above 15 m in height and in special occupancies, like educational, assembly, institutional, industrial, storage, hazardous and mixed occupancies with any of the aforesaid occupancies having area more than 500 m2 on each floor, provision shall be made for an independent and ventilated meter (service) room, as per requirements of electric (service) supply undertakings on the ground floor with direct access from outside for the purpose of termination of electric supply from the licensee’s service and alternative supply cables. The door/doors provided for the service room shall have fire resistance of not less than two hours.
5.1.16 Roofs
5.1.16.1 The roof of a building shall be so designed and constructed as to effectively drain water by means of sufficient rain-water pipes of adequate size, wherever required, so arranged, jointed and fixed as to ensure that the rain-water is carried away from the building without causing dampness in any part of the walls, roof or foundations of the building or an adjacent building
(1) The Authority may require rain-water pipes to be connected to a drain or sewer to a covered channel formed beneath the public footpath to connect the rainwater pipe to the road gutter or in any other approved manner.
(2) Rain-water pipes shall be affixed to the outside of the external walls of the building or in recesses or chases cut or formed in such external walls or in such other manner as may be approved by the Authority.
(3) It is desirable to conserve rain water using suitable rain water harvesting techniques including by roof water collection. In this context, reference may be made to Part 9 ‘Plumbing Services, Section 1 Water Supply, Drainage and Sanitation (Including Solid Waste Management)’ of NBC, 2016.