5.1 Requirements for Parts of Buildings 5.1.1Plinth
5.1.1.1 The plinth or any part of a building or outhouse shall be so located with respect to the surrounding ground level that adequate drainage of the site is assured. The height of the plinth shall be not less than 450 mm from the surrounding ground level, in case of independent houses and not less than 300mm in case of other buildings.
5.1.1.2 Interior Courtyards and Covered Parking: Every interior courtyard shall be raised at least 150 mm above the determining ground level and shall be satisfactorily drained.
5.1.2 Habitable Rooms
5.1.2.1 Height.- The clear height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab) provided that the minimum clear headway under any beam shall not be less than 2.4m In the case of pitched roof, the average height of rooms shall not be less than 2.75m. The minimum clear head room under a beam, folded plates or eaves shall be 2.4m. In the case of air-conditioned rooms, a height of not less than 2.4m measured from the surface of the floor to the lowest point of airconditioning duct or the false ceiling shall be provided.
5.1.2.2 The requirements of clause 5.1.2.1 shall apply to residential, business and mercantile buildings. For educational and industrial buildings, the following minimum requirements apply:
Table 5.1Minimum height requirement for educational and industrial buildings
Sl. No
Type of Occupancy
Ceiling height
1
Educational Buildings
Ceiling height 3.6m for all regions
2
Industrial Buildings
Ceiling height 3.6m, except when air-conditioned, 3m (Factory Act 1948 and Rules therein shall govern such heights, where applicable)
5.1.2.3 Size.- The area of habitable room shall not be less than 9.5Sqm, where there is only one room with a minimum width of 2.4m. Where there are two rooms, one of these shall not be less than 9.5Sq.m and the other not less than 7.5Sq.m, with a minimum width of 2.1m.
5.1.3 Kitchen
5.1.3.1 Height.- The height of a kitchen measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.75 m, except for the portion to accommodate floor trap of the upper floor.
5.1.3.2 Size.- The area of a kitchen where separate dining area is provided shall be not less than 5.0Sq.m with a minimum width of 1.8m. Where there is a separate store, the area of the kitchen may be reduced to 4.5Sq.m. A kitchen, which is intended for use as a dining area also, shall have a floor area of not less than 7.5 Sq.m with a minimum width of 2.1m.
5.1.3.3 Other Requirements.- Every room to be used as kitchen shall have:
(a) Unless separately provided in a pantry, means for the washing of kitchen utensils which shall lead directly or through a sink to a grated and trapped connection to the waste pipe;
(b) An impermeable floor; and
(c) A flue, if found necessary
5.1.4Bathrooms and Water-Closets
5.1.4.1 Height.- The height of a bathroom or water-closet measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.1m.
5.1.4.2 Size.- The area of a bathroom shall not be less than 1.8 Sq.m with a minimum width of 1.2m. The floor area of water-closet shall be 1.1Sq.m with a minimum width of 0.9m. If
bath and water-closet are combined, its floor area shall not be less than 2.8Sq.m with a minimum width of 1.2m.
5.1.4.3 Other Requirements.- Every bathroom or water-closet shall:
(a) Be so situated that at least one of its walls shall face a shaft or open space
(b) Not be directly over or under any room other than another water-closet, washing place, bath or terrace, unless it has a water-tight floor;
(c) Have the platform or seat made of water-tight non-absorbent material;
(d) be enclosed by walls or partitions and the surface of every such wall or partition shall be finished with a smooth impervious material to a height of not less than 1 m above the floor of such a room;
(e) Be provided with an impervious floor covering, sloping towards the drain with a suitable grade and not towards VERANDAH or any other room; and
(f) Have a window or ventilator, opening to a shaft or open space, of area not less than 0.3Sq.m with side not less than 0.3m.
5.1.4.4 No room containing water closets shall be used for any purpose except as a lavatory and no such room shall open directly into any kitchen or cooking space by a door, window or other opening. Every room containing water-closet shall have a door completely closing the entrance to it.
5.1.5 Loft
5.1.5.1 Height.- The minimum head-room of loft shall be 2.2m.
5.1.5.2 Size.- A loft in a habitable room shall not cover more than 25 percent of the area of the floor on which it is constructed and shall not interfere with the ventilation of the room under any circumstances.
5.1.9 Basement
5.1.9.1 The Authority in accordance with the land use and other provisions specified under the Zonal Regulations shall allow the construction and usage of the basement
5.1.9.2 The basement shall have the following requirements:
(a) Every basement shall be in every part at least 2.4 m in height from the floor to the underside of the roof slab/beam joists and at any part shall not exceed 4.5m in height;
(b) Adequate ventilation shall be provided for the basement. The ventilation requirements shall be the same as required by the particular occupancy according to byelaws. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans, air-conditioning systems, etc.
(c) The maximum height at the top of the roof slab of the basement floor shall not be more than 1.2m above the average surrounding ground level;
(d) Adequate arrangements shall be made such that surface drainage does not enter the basement;
(e) The walls and floors of the basement shall be watertight and be so designed that the effects of the surrounding soil and moisture, if any, are taken into account in design and adequate damp proofing treatment is given; and
(f) The access to the basement shall be separate from the main and alternative staircase providing access and exit from higher floors.
(g) Where the staircase is continuous in the case of buildings served by more than one staircase, the same shall be of enclosed type serving as a fire separation from the basement floor and higher floors. Open ramps shall be permitted if they are constructed within the building line subject to the provision of (d). The exit requirements in basements shall comply with the provisions of these Byelaws.
5.1.10 Chimneys.- The chimneys shall be built at least 0.9 m above flat roofs, provided the top of the chimneys is not below the top of the adjacent parapet wall. In the case of sloping roofs, the chimney top shall not be less than 0.6 m above the ridge of the roof in which the chimney penetrates.
5.1.11 Parapet.- Parapet walls and handrails provided on the edges of roof terraces, balcony, verandah, etc. shall not be less than 1.0 m and not more than 1.2 m in height from the finished floor level.
(i). The above shall not apply where roof terrace is not accessible by a staircase.
(ii). However on terrace floor in the portion where installations like DG Set, Water Tank and other, screening parapet of a suitable height may be constructed to hide such equipment’s etc. and there is no need to have uniform increase in the height of the parapet.
5.1.12 Boundary Wall.- The requirements of the boundary wall shall be as follows:
(a) Except with the special permission of the Authority, the maximum height of the compound wall shall be 1.5 m above the Centre line of the front street. Compound wall up to 2.4 m height may be permitted if the top 0.9 m is of open type construction of a design to be approved by the Authority.
5.1.16 Roofs
5.1.16.1 The roof of a building shall be so designed and constructed as to effectively drain water by means of sufficient rain-water pipes of adequate size, wherever required, so arranged, jointed and fixed as to ensure that the rain-water is carried away from the building without causing dampness in any part of the walls, roof or foundations of the building or an adjacent building
(1) The Authority may require rain-water pipes to be connected to a drain or sewer to a covered channel formed beneath the public footpath to connect the rainwater pipe to the road gutter or in any other approved manner;
(2) Rain-water pipes shall be affixed to the outside of the external walls of the building or in recesses or chases cut or formed in such external walls or in such other manner as may be approved by the Authority; and
(3) It is desirable to conserve rain water using suitable rain water harvesting techniques including by roof water collection. In this context, reference may be made to Part 9 ‘Plumbing Services, Section 1 Water Supply, Drainage and Sanitation (Including Solid Waste Management)’ of NBC, 2016.
5.2Other general requirements
5.2.1Swimming Pool
(1) Definition: A constructed pool or a tank indoor or outdoor, used for the purpose of swimming, bathing, aquatic sports or games, training, treatment (Therapy) or recreation, meant exclusively for human being, having a depth of water not less than that 60cm and the surface area exceeding 23.25 Sq.m both for the use of public or the institution concerned.
a. ‘Capacity of Pools in Relation to Bathers’: The maximum number of persons in bathing attire within the pool enclosures of the bathing area shall not exceed one person per 20Sft (1.86Sq.m) of pool i.e. the area of the water surface.
(2) ‘Hand Rail’: A side handrail extending up above and returning to the horizontal surface of the pool deck curb or coping shall be provided at each side of each ladder.
(3) ‘Depth Markers’: Depth of water shall be clearly marked at or above the water surface on the vertical pool wall and on the edge of the deck or walk-way next to the pool, at maximum points and at the points of break between the deep and shallow portions and at intermediate increments of depth, spaced at not more than 2.5’ (7.62cm) intervals. Depth markers, contrasting with background shall be on both sides of the pool.
(4) ‘Lighting and wiring’: Where submarine lightning is used, not less than 0.5 watts shall be employed per sq. ft. of pool area.
(5) ‘Area Lightning’: Where submarine lightning is employed, area lightning shall be provided for the deck areas and directed towards the deck areas and away from the pool surface so far as practicable, in a total capacity of not less than 0.6 watt per Sft of deck area.
Where submarine lighting is not provided and night swimming is not permitted combined pool lightning shall be provided in an amount of not less than 2 watts per Sft. of total area. All submarine lightning shall be individually earthed and must be water tight and damp proof.
(6) ‘Over Head wiring’: No electrical wiring for electrical or power shall be permitted to pass over within 20 feet of the pool enclosure.
(7) ‘Shallow Minimum Depth’: Every swimming pool shall have a minimum depth in the shallow area of the main swimming area of not less than 0.9m (3 feet), but not more than 1.07m (3’- 6’) from the overflow level to the floor.
(8) ‘Shallow Areas’: In a swimming pool with a diving area, the shallow area of the pool shall be defined as the portion between the shallow end and the break point between the shallow area and the diving area. The slope of the floor shall be uniform from the break point between the diving area and the shallow portion to the outside edge of the shallow portion and shall not be greater than 1 in 2m.
(9) ‘Vertical Wall Depth’: The pool walls shall be vertical at all points for a depth of not less than 0.76m.
5.2.2Means of access
5.2.2.1 No Building shall be erected as to deprive any other building of its means of access.
5.2.2.2 Every person who erects a building shall not at any time erect or cause or permit to erect or re- erect any building, which in any way encroaches upon or diminishes the area set apart as means of access.
5.2.2.3 The Means of Access prescribed in the Zonal Regulations shall be considered while sanctioning Building Licence. The portion of the plot required for widening the road to the proposed width shall be relinquished free of cost without claiming any compensation (including DR), before sanctioning Building Licence.
5.2.3Staircase Requirements
5.2.3.1 The minimum clear width, minimum tread width and maximum riser of staircases for buildings shall be as given as below (see also Part 4 ‘Fire and Life Safety of NBC 2016).
5.2.3.2 Minimum width
Table 5.2The minimum width of staircase
A
i) Residential buildings (dwellings) ii) Apartment buildings NOTE - For row housing with 2 storeys, the min. width shall be 0.75m
1.0m1.25m
B
Hotel buildings/Lodging House
1.5m
C
Assembly buildings like auditoria, theatres and cinemas
2.0m
D
Educational building
1.5m
E
Institutional buildings
2.0m
F
All other buildings
1.5m
5.2.3.3 Minimum tread.- The minimum width of tread without nosing shall be 250 mm for residential buildings. The minimum width of tread for other buildings shall be 300mm.
5.2.3.4 Maximum riser
5.3.2.4.1 The maximum height of riser shall be 190mm for residential buildings and 150mm for other buildings and these shall be limited to 12 per flight. The maximum height of riser shall be 190mm for residential buildings and 150mm for other buildings and these shall be limited to 12 per flight.
5.3.2.4.2 The minimum head-room in a passage under the landing of a staircase shall be 2m. The minimum clear head-room in any staircase shall be 2.1m.
5.2.4 Exit Requirements.- All aspects of exit requirements for corridors, doors, stair cases, ramps, etc. in respect of widths, travel distance shall be as prescribed in these Byelaws.
5.2.4.1 Occupant Load.- The following occupant load shall be considered for calculating the exit requirement of the building
Table 5.3Occupant Load
Sl. No.
Type of Occupancy
Occupant Load per 100Sq.m of Carpet Area (in persons)
1
Residential
8.0
2
Educational
25.0
3
Institutional
6.60
4
Assembly With fixed or loose seats and dance floor without seating facilities including dining rooms
166.666.6
5
Mercantile Street floor and sales basement Upper sale floor
33.316.6
6
Business and industrial
10.0
7
Storage
3.3
8
Hazardous
10.0
Note: The occupant load in dormitory potions of homes for the aged, orphanages or mental hospitals etc. where sleeping accommodation is provided shall be calculated at not less than 13.3 persons per 100Sq.m
(2). In case of assembly occupancy, all rooms, toilets common areas connected to the assembly occupancy shall be included in the carpet area for calculating the occupancy load.
5.2.4.2 Number and size of Exits.- The requisite number and size of various exits shall be provided, based on the occupants in each room and floor based on the occupant load, capacity of exits, travel distance and height of buildings as prescribed in these Byelaws.
At least one primary entrance to each building shall be usable by individuals in wheelchairs and shall be indicated by a sign. At least one entrance usable by individuals in wheelchairs shall be on a level that would make the elevators accessible.
5.2.4.3 Arrangement of Exits
(1) Exits shall be so located so that the travel distance on the floor shall not exceed 30m for residential, educational, institutional assembly, business, mercantile and storage occupancies, 45.0m for industrial occupancy and 22.5m for hazardous building. For fully sprinklered building, the travel distance may be increased by 50 percent of the above values. Whenever more than one exit is required for a floor of a building they shall be placed as remote from each other as possible. All the exits shall be accessible from the entire floor area at all floor levels, where separate fire separation walls are not provided.
(2) The travel distance to an exit from the dead end of the corridor, if applicable, shall not exceed half the distance as stated above except in the case of institutional occupancy in which case it shall not exceed 6.0m.
5.2.4.4 Capacity of Exits.- The capacity of exits (staircase, ramps and doorways) indicating the number of persons that could be safely evacuated through a unit exit width of 50 cm shall be as given below:
Table 5.4Occupants per unit Exit width
Sl. No.
Group of Occupancy
Number of Occupants
Stairway s
Ramp s
Doors
1
Residential
25
50
75
2
Educational
25
50
75
3
Institutional
25
50
75
4
Assembly
40
50
60
5
Business
50
60
75
6
Mercantile
50
60
75
7
Industrial
50
60
75
8
Storage
50
60
75
9
Hazardous
25
30
40
5.2.4.5 Minimum Width Provisions for Passageway/Corridors
The following minimum width provisions shall be made for each passage way/corridor.
(a) Residential buildings, upto 4 dwelling units 1.00m
(b) Apartment buildings, hostels, etc. 1.25m
(c) Assembly buildings like auditorium theatres and cinemas 2.00m.
(d) All other buildings including hotels 1.50m
(e) Hospital, Nursing Homes, etc. 2.40m
5.2.5Ramps
(1) The ramp to basement and parking floors shall be as prescribed in the Zonal Regulations.
(2)Ramps may also be provided in the setbacks to function as fire drive cum ramp for basements, which can be sloped considering unhindered movement of fire engine and in no case the gradient shall be steeper than 1 in 10 for Plains and steeper than 1 in 8 for Hilly areas.
(3)All structural design/safety aspects as per latest BIS Codes and NBC 2016 shall be complied along with consideration of weight of Fire Engine and its manoeuvrings.
(4) The minimum width of the ramps in hospitals shall be 2.4m for stretcher and not for vehicular movement.
(5) In this case Handrails shall be provided on both sides of the ramp.
(6)Ramps shall lead directly to outside open space at ground level or courtyards or safe place 5.2.6 Doorways
(1) Every doorway shall open into an enclosed stairway, a horizontal exit, on a corridor or passageway providing continuous and protected means of egress
(2) No exit doorways shall be less than 1m in width except assembly and institutional buildings where Doorway shall not be less than 2m.
(3) Exit doorways shall open outwards, that is away from the room but shall not obstruct the travel along any exit. No door when opened shall reduce the required width of stairway or landing to less than 0.90m Overhead or sliding door shall not be installed.
Note: In the case of buildings where there is a central corridor, the doors of rooms shall open inwards to permit smooth flow of traffic in the corridor
(4) Exit door shall not open immediately upon a flight of stairs. A landing equal to at least, the width of the door shall be provided in the stairway at each doorway. Level of landings shall be the same as that of the floor, which it serves.
(5) Exit doorways shall be open-able from the side, which they serve without the use of a key.
(6) Revolving doors shall not to be provided as means of fire exit.
(7) Mirrors shall not be placed in exit ways or exit doors to avoid confusion regarding the direction of exit.
5.2.7Provision of exterior open spaces and height limitation around the building
5.2.7.1 The open spaces/setbacks, coverage, FAR, parking requirements shall be as per Zonal regulations of the Master Plan
5.2.7.2 Every room that is intended for human habitation shall abut on an interior or exterior open space or on to a verandah open to such interior or exterior open space. In case of High rise the driveway in exterior open spaces around a building shall be of green or hard surface capable of taking load of fire engine weighing up to 45 ton
5.2.7.3 In case, kitchen and toilets do not about either interior or exterior open spaces, mechanical ventilation would be accepted.
5.2.8Interior Open Space for Light and Ventilation
5.2.8.1 The whole or part of one side of one or more rooms intended for human habitation and not abutting on either the front, rear or side open spaces shall abut on an interior open space whose minimum width in all directions shall be 3m in case of buildings not more than 15m in height, and in case of high-rise buildings it shall have mandatory mechanical ventilation in addition
5.2.8.2 Sunken Courtyard.- Sunken courtyard up to 3m in depth from the ground level as ‘light well’ within building envelop shall be permitted for light and ventilation for basement area.
5.2.8.3 Skylight.- Skylight in interior open space (courtyard) shall be permitted subject to the fact that it may not act as a covered space on the ground floor and does not violate the maximum/minimum ground coverage rules.
5.2.9Lighting and ventilation of rooms
5.2.9.1 IS Codes for lighting and ventilation requirements.- Rooms shall have, for the admission of light and air, one or more openings, such as windows and ventilators, opening directly to the external air or into an open VERANDAH.
Lighting and ventilation requirements of all types of buildings shall be designed and approved in accordance with the provisions of the following two IS Codes –
(a). SP 32 (1986): Hand book on Functional Requirements of Industrial Buildings (Lighting and Ventilation) [CED 12: Functional Requirements in Buildings] and
(b). SP 41 (1987): Hand book on Functional Requirements of Buildings (Other than Industrial Buildings) [CED 12: Functional Requirements in Buildings]
Lighting loads of various spaces of –
(a). Industrial buildings shall be determined as per Clause 1, Section 1 of SP 32(1986)
(b). Non-Industrial buildings shall be determined as per Clause 2, Part 4 of SP 41(1987)
Thermal comfort levels and design requirement of various spaces of –
(a). Industrial buildings shall be determined as per Section 2 of SP 32 (1986)
(b). Non-Industrial buildings shall be determined as per Part 2 of SP 41 (1987) Minimum Fresh Air requirement for –
(a). Industrial buildings shall be determined as per Clause 13 of Section 2 of SP 32(1986)
(b). Non-Industrial buildings shall be determined as per Clause 4 of Part 3 of SP 41(1987)
5.2.9.2 The minimum aggregate area of openings.- The minimum aggregate area of such openings, excluding doors inclusive of frames, shall be not less than one-sixth of the floor area. Openable part of French window shall be considered as openings for applying this clause.
(i). If a window is partly fixed, the openable area shall be counted
(ii) No portion of a room shall be assumed to be lighted, if it is more than 7.5m away from the opening assumed for lighting that portion.
(iii) The area of openings as given above shall be increased by 25 percent in the case of a kitchen.
(2) All habitable rooms shall have for the admission of light and air, one or more apertures, such as window, glazed door, opening directly to the external air or into an open verandah not more than 2.40m in width. In case light and ventilation to habitable space area are through an internal courtyard, the minimum dimensions of such courtyard shall not be less than 3.0m x 3.0m for buildings up to 12.50m in height. For buildings with higher heights, the minimum dimensions of the internal courtyard shall be as given in these Bye-Laws.
(3) Where the lighting and ventilation requirements are not met through day lighting and natural ventilation, the same shall be ensured through artificial lighting and mechanical ventilation as given in part-VII building services Section-1 lighting and Ventilation of National Building Code of India published by the Bureau of Indian Standards. The latest version of the National Building Code of India shall be taken into account at the time of enforcement of the Building Bye-Laws.
5.2.9.3 Ventilation Shaft.- For ventilating the spaces for water closets and bathrooms, if not opening on the front side, rear and interior open spaces, shall open on the ventilation shaft, the size, of which shall not be less than the values given below:
Table 5.5Size of Ventilation Shaft
Height of Building
Size of ventilation
Minimum size of
(m)
shaft (Sq.m)
shaft (m)
Up to 10.0
1.2
0.9
Up to 12.0
2.8
1.2
Up to 18.0
4.0
1.5
Up to 24.0
5.4
1.8
Up to 30.0
8.0
2.4
Above 30.0
9.0
3.0
Notes:
i. For buildings above 30.0m height, mechanical ventilation system shall be installed besides the provision of minimum ventilation shaft.
(ii) For fully air-conditioned buildings the ventilation shaft need not be insisted upon, provided the air-conditioning system works in an uninterrupted manner, also, provided there is an alternative source of power supply. However, it is not mandatory in case of buildings where ventilation is mechanized
5.3Building Services
5.3.1 Electrical, Air conditioning, Lift and Escalator installations
5.3.1.1 Planning, design and installations of electrical, air-conditioning and lift installations.- The Planning design and installation of electrical installations, air conditioning installation of lifts and escalators can be carried out in accordance with Part-7 Building Services, section–2 electrical installation, section–3 air conditioning and heating, section-5 installation of lifts and escalators of National Building Code of India. However, deviations from National Building Code may be done as per good Engineering practices.
5.3.1.2 Number and types of lifts
(1) Lift shall have to be provided for buildings with more than ground plus three floors.
(2) The number and type of lifts to be provided in different buildings shall be as given in Appendix-XIIIA.
5.3.1.3 Requirements of Electrical substation.- The requirements of electric substation are given in Appendix-XIIIB. The provision of electric sub-station shall also require approval from Electricity Board concerned.
5.3.2Plumbing and Sanitary Services
5.3.2.1 Planning, design, construction and installation of Water supply, drainage and sanitation and gas supply system.- The planning, design, construction and installation of water supply, drainage and sanitation and gas supply system shall be in accordance with Part-9: Plumbing Services, Section-l Water supply, Drainage and sanitation (including Solid Waste Management) and Section-2 Gas supply of NBC, 2016.
5.3.2.2 Norms for differently-abled within segregated toilets
(i). One special W.C. in a set of toilet shall be provided for the use of differently abled persons, with essential provision of wash basin near the entrance.
(ii). Minimum clear opening of the door shall be 900mm and the door shall swing out.
(iii). Minimum clear opening of the door shall be 900mm and the door shall swing out.
(iv). Suitable arrangement of vertical/horizontal handrails with 50mm clearance from wall shall be made in the toilet.
(v). The W.C. seat shall be 500mm from the floor.
5.3.2.3 Water requirement and facilities.- Water requirement for the facility may be worked out and enough storage for ½ day operation is to be kept in storage. If municipal water supply is reliable, the toilet blocks may have underground sump that can store half a day requirement and overhead tanks for another half. If municipal water supply is not available, toilet block may have its own water source and pump with or without underground sump.
Alternatively, a hand tube well can be used for storing water in an elevated (not overhead) tank. To minimize the wastage of water, self-closing water taps should be used. The pans must be of Pour Flush (PF) design i.e. with a steep slope. Traps should be of a 20mm water seal. (Use of 50mm water seal traps will require more water for flushing.) If toilet is to be linked to city sewer, a master trap has to be provided at the sewer connection for waste water line (excluding soil line).
Table 5.6Water Requirements for Various Occupancies / Uses (Ref. NBC 2016 Part 9, Section 1, Clause 4.1.1, 4.1.2 and Table 1)
Sl. No.
Type of Building
Domestic Per day litre
Flushing Per Day litre
Total Consumption Per Day litre
i)
Residences a) For communities with population up to20,0001) Water supply through stand post 2) Water supply through house service connection (70 to 100 lphd)
40 lphd (Min) 100 lphd
i)
b) For communities with Population 20 000 to 100 000 (100 to 135 lphd)
95 lphd
45 lphd
135 lphd
i)
c) For communities with Population above 100 000 (150 to 200 lphd)
155 lphd
45 lphd
200 lphd
i)
NOTE: The value of water supply given as 150 to 200 litre per head per day may be reduced to 135 lphd for houses for Medium Income Group (MIG) and Lower Income Groups (LIG) and Economically Weaker Section (EWS), depending upon prevailing conditions and availability of water.
ii)
Factories including canteen where bath rooms are required to be provided
30 per head
15 per head
45 per head
iii)
Factories including canteen where no bath rooms are required to be provided
20 per head
10 per head
30 per head
iv)
Hospital (excluding laundry and kitchen (see Note2):a) Number of beds not exceeding 100
230 per head
110 per head
340 per head
iv)
b) Number of beds exceeding 100
300 per head
150 per head
450 per head
iv)
c) Outpatient department (ODP)
10 per head
5 per head
15 per head
v)
Nurses homes and medical quarters
90 per head
45 per head
135 per head
vi)
Hostels
90 per head
45 per head
135 per head
vii)
Hotel (up to 3 start) excluding laundry, kitchen, staff and water bodies
120 per head
60 per head
180 per head
viii)
Hotel (4 star and above) excluding laundry, kitchen, staff and water bodies.
260 per head
60 per head
320 per head
ix)
Offices (including canteen)
25 per head
20 per head
45 per head
x)
Restaurants and food court including water requirement for kitchen: a) Restaurants
55 per head
15 per head
70 per head
x)
b) Food court
25 per head
10 per head
35 per head
xi)
Clubhouse
25 per head
20 Per head
45 per head
xii)
Stadiums
4 per head
6per head
10 per head
xiii)
Cinemas, Concert halls and theatres and multiplex
5 per head
10 per head
15 per head
xiv)
Schools/Educational institutions: a) Without boarding facilities
25 per head
20 per head
45 per head
xiv)
b) With boarding facilities
90 per head
45 per head
135 per head
Sl. No.
Type of Building
Domestic Per day litre
Flushing Per Day litre
Total Consumption Per Day litre
xv)
Shopping and retail (mall) a) Staff
25 per head
20 per head
45 per head
xv)
b) Visitors
5 per head
10 per head
15 per head
xvi)
Traffic terminal stations (see Notes 3 and 4) a) Airports
40 per head
30 Per head
70 per head
xvi)
b) Railway stations (Junctions) with bathing facility
40 per head
30 per head
70 per head
xvi)
c) Railway stations (Junctions) without bathing facility
30 per head
15 per head
45 per head
xvi)
d) Railway stations (Intermediate) with bathing facility
25perhead
20 per head
45 per head
xvi)
e) Railway stations (Intermediate) without bathing facility
15 per head
10 per head
25 per head
xvi)
f) Interstate bus terminals
25 per head
20 per head
45 per head
xvi)
g) Interstate Bus Terminals/ Metro Stations
10 per head
5 per head
15 per head
NOTES:
(1) For Calculating water demand for visitors, consumption of 15 litre per head per day may be taken.
(2) The Water demand includes requirement of patients, attendants, visitors and staff. Additional water demand for kitchen, laundry and clinical water shall be computed as per actual requirements.
(3) The number of persons shall be determined by average number of passengers handled by stations, with due considerations given to the staff and vendors who are using these facilities.
(4) Consideration should be given for seasonal average peak requirements.
(5) The hospitals may be categorized as Category A (25 to 50 beds), Category B (51 to 100 beds), Category C (101 to 300 beds), Category D (301 to 500) and Category E (501 to 750 beds),
Executive Rooms and Conference Halls in Office Buildings
Executive Rooms and Conference Halls in Office Buildings
Executive Rooms and Conference Halls in Office Buildings
Executive Rooms and Conference Halls in Office Buildings
Executive Rooms and Conference Halls in Office Buildings
Executive Rooms and Conference Halls in Office Buildings
i)
Toilet suite comprising one WC, one wash basin (with optional shower stall if building is used round the clock at user's option) Pantry optional as per user requirement Main Office Toilets for Staff and Visitors
Unit could be common for male / female or separate depending on the number of user of each facility
Unit could be common for male / female or separate depending on the number of user of each facility
For individual officer rooms
For individual officer rooms
Sl. No.
Fixtures
Public Toilets
Public Toilets
Staff Toilets
Staff Toilets
Sl. No.
Fixtures
Males
Females
Males
Females
(1)
(2)
(3)
(4)
(5)
(6)
ii)
Water closets
See Note
See Note
1 per 25
1 per 15
iii)
Ablution tap with each water closet
1 in each water closet
1 in each water closet
1 in each water closet
1 in each water closet
iv)
Urinals
See Note
-
Nil up to 6 1 for 7 to 20 2 for 21 to 45 3 for 46 to 70 4 for 71 to 100 From 101 to 200, add @ 3% For over 200, Add @ 2.5%
-
v)
Wash basins
See Note
1 per 25
1 per 25
vi)
Drinking water fountain
See Note
1 per 100
1 per 100
vii)
Cleaner's sink
1 per floor
1 per floor
1 per floor
1 per floor
NOTE: Staff and public toilet utilities are generally common in office buildings. Where public toilets are to be provided independently, similar requirements as that of staff toilet may be provided.
1 per 100 up to400Over 400 add at 1 per 250 or part thereof
3 per 100 up to200Over 200 add at 2 per 100 or part thereof
1 for up to 15 2 for 16 to 35
1 for up to 12 2 for 13 to 25
ii)
Ablution tap
1 in each water closet
1 in each water closet
1 in each water closet
1 in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iii)
Urinals
1 per 25 or part thereof
-
Nil up to 6 1 for 7 to 20 2 for 21 to 45
-
iv)
Wash basins
1 per 200 or part thereof
1 for up to 15 2 for 16 to 35
1 for up to 12 2 for 13 to 25
v)
Drinking water fountain
1 per 100 persons or part thereof
vi)
Cleaner's sink
1 per floor
vii)
Showers / bathing rooms
As per trade requirements
NOTES 1. Some WCs may be Indian style, if desired 2. Male population may be assumed a two - third and female population as one-third
Table 5.11Sanitation Requirements for Art Galleries, Libraries and Museums (Ref. NBC 2016 Part 9, Section 2, Clause 4.2.5.1, Table 4)
Sl. No.
Fixtures
Public
Public
Staff
Staff
Sl. No.
Fixtures
Males
Females
Males
Females
1
2
3
4
5
6
i)
Water Closets
1 per 200 upto 400 over 400 add at 1 per 250 or part thereof
1 per 100 up to 200 Over 200 add at 1 per 150 or part thereof
1 for upto 15 2 for 16 to 35
1 for upto 12 2 for 13 to 25
ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
One water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
One water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
One water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
One water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
One water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
Sl.No.
Fixtures
Public
Public
Staff
Staff
Sl.No.
Fixtures
Males
Females
Males
Females
1
2
3
4
5
6
iii)
Urinals
1 per 50
-
Nil up to 61 per 7 to 202 per 21 to 45
-
iv)
Wash basins
1 for every 200 or part thereof. For over 400, add at 1 per 250 persons or part thereof
1 for every 200 or part thereof. For over 200, add at 1 per 150 persons or part thereof
1 for up to 152 for 16 to 35
1 for up to 122 for 13 to 25
v)
Drinking water fountain
Table 5.12Sanitation Requirements for Hospitals with Indoor Patient Wards (Ref. NBC 2016 Part 9, Section 2, Clause 4.2.5.1, Table 5)
Sl. No.
Fixtures
Public
Staff
Males
Females
Males
Females
1
2
3
4
5
6
i)
Toilet suit comprising one WC and one wash basin and shower stall
Private room with up to 4 patients
For individual doctor's / officer's rooms
For General Wards, Hospital Staff and Visitors
ii)
Water Closets
1 per 5 beds or part thereof
1 per 5 beds or part thereof
1 for up to 15 2 for 16 to 35
1 for up to 12 2 for 13 to 25
iii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
iv)
Urinals
1 per 15 beds
-
Nil up to 6 1 for 7 to 20 2 for 21 to 45
-
v)
Wash basins
2 for every 30 beds or part thereof. Add 1 per additional 30 beds or part thereof
1 for up to 15 2 for 16 to 35
1 for up to 12 2 for 13 to 25
vi)
Drinking water fountain
1 per ward
1 per 100 persons or part thereof
vii)
Cleaner's sink
1 per ward
-
viii)
Bed pan sink
1 per ward
-
ix)
Kitchen sink
1 per ward
-
NOTES: 1. Some WCs may be of Indian style, if desired. 2. Male population may be assumed as two-third and female population as one-third. 3. Provision for additional and special hospital fittings where required shall be made. 4. Drinking water fountains are not recommended for hospitals for reasons of infection control. This is to be decided by the health authority recommendations.
Table 5.13Sanitation Requirements for Hospitals with Outdoor Patient Department (Ref. NBC 2016 Part 9, Section 2, Clause 4.2.5.1, Table 6)
Sl. No.
Fixtures
Patient Toilets
Staff Toilets
Males
Females
Males
Females
1
2
3
4
5
6
i)
Toilet suit comprising one WC and one wash basin (with optional shower stall if building used for 24 h)
For up to 4 patients
For individual doctor's / officer's rooms
ii)
Water Closets
1 per 100 persons or part thereof
2 per 100 persons or part thereof
1 for up to 15 2 for 16 to 35
1 for up to 12 2 for 13 to 25
iii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iv)
Urinals
1 per 50 persons or part thereof
-
Nil up to 6 1 for 7 to 20 2 for 21 to 45
-
v)
Wash basins
2 per 100 persons of part thereof
2 per 100 persons or part thereof
1 for up to 15 2 for 16 to 35
1 for up to 12 2 for 13 to 25
vi)
Drinking water fountain
See Note 2
1 per 100 persons or part thereof
NOTES: (1) Some WCs may be of Indian style, if desired. (2) Drinking water fountains are not recommended for hospitals for reasons of infection control. This to be decided by the health authority recommendation. (3) The WCs shall be provided keeping in view the location of main OPD waiting hall and sub-waiting hall and sub-waiting halls, floor wise, so as to serve the people effectively. The number of patients shall be calculated floor wise. The OPD population shall include patient attendants @ least 1 per patient. (4) Male population may be assumed as two-third and female population as one-third. (5) Provision for additional and special hospital fittings where required shall be made.
Table 5.14Sanitation Requirements for Hospitals, administrative Buildings (Ref. NBC 2016 Part 9, Section 2, Clause 4.2.5.1, Table 7)
Sl. No.
Fixtures
Staff Toilets
Males
Females
1
2
3
4
i)
Toilet suite comprising one WC, one urinal and one wash basin (with optional shower stall if building used for 24 h)
For individual doctor's / officer's rooms
ii)
Water Closets
1 per 25 persons or part thereof
1 per 15 persons or part thereof
iii)
Ablution tap
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
iv)
Urinals
1 for 6 to 15 2 for 16 to 50
-
v)
Wash basins
1 per 25 persons or part thereof
1 per 25 persons or part thereof
vi)
Drinking water fountain
1 per 100 persons or part thereof (See Note 2)
vii)
Cleaner's sink
1 per floor, Min.
viii)
Kitchen sink
1 per floor, Min.
Some WCs may be of Indian style, if desired.
Drinking water fountains to be provided only when it is a separate block and patients will not use it.
Table 5.15Sanitation Requirements for Hospitals Staff Quarters and Nurses Homes (Ref. NBC 2016 Part 9, Section 2, Clause 4.2.5.1, Table 8)
Sl. No
Fixtures
Staff Quarters
Nurses
(1)
(2)
Males
Females
Males
Females
(3)
(4)
(5)
(6)
(i)
Water closets
1 per 4 persons or part thereof
1 per 4 persons or part thereof
1 per 4 persons or part thereof 2 for 5 to 35
1 per 4 persons or part thereof 2 for 5 to 25
(ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
I water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
(iii)
Wash basins
1 per 8 persons or part thereof
1 per 8 persons or part thereof
(iv)
Bath (showers)
1 per 4 persons or part thereof
1 per 4 persons or part thereof
(v)
Drinking water fountain
1 per 100 persons or part thereof, Min 1 per floor
1 per 100 persons or part thereof, Min 1 per floor
(vi)
Cleaner's sink
1 per floor
1 per floor
NOTES: (1) Some WCs may be Indian style, if desired (2) For independent housing units, fixtures shall be provided as for residences
1 per 50 seats up to 200 Over 200 add at 1 per 100 or part thereof
2 per 50 seats up to 200 Over 200 add at 1 per 100 or part thereof
1 for up to 15 2 for 16 to 35 3 for 36 to 65 4 for 66 to100
1 for up to 12 2 for 13 to 25 3 for 26 to 40 4 for 41 to 57 5 for 58 to 77 6 for 78 to 100
ii.
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
I water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
iii.
Urinals
1 per 50 persons or part thereof
-
Nil up to 6 1 for 7 to 20 2 for 21 to 45 3 for 46 to 70 4 for 71 to100
-
iv.
Wash basins
1 per WC
1 per WC
1 per WC
1 per WC
v.
Cleaner's sink
1 per each restaurant
vi.
Kitchen sink/dishwasher
1 per Kitchen
NOTES: (1) Some WCs may be Indian style, if desired (2) Male population may be assumed as two-third and female populations one-third. (3) Provision for additional and special fitting where required shall be made.
Table 5.18Sanitation Requirements for Schools and Educational Institutions (Ref. NBC 2016 Part 9, Section 2, Clause 4.2.5.1, Table 11)
Sl. No
Fixtures
Nursery School
Public Rooms
Public Rooms
Non-Residential staff
Non-Residential staff
(1)
(2)
(3)
Boys
Girls
Boys
Girls
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(i)
Water closets
1 per 15 pupils or part thereof
1 per 40 pupils or part thereof
1 per 25 pupils or part thereof
1 per 8 pupils or part thereof
1 per 6 pupils or part thereof
(ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
(ii)
I water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
I water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
I water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
I water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
I water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals.
(iii)
Urinals
-
1 per 20 pupils or part thereof
-
1 per 25 pupils or part thereof
-
(iv)
Wash basins
1 per 15 pupils or part thereof
1 per 60 pupils or part thereof
1 per 40 pupils or part thereof
1 per 8 pupils or part thereof
1 per 6 pupils or part thereof
(v)
Bath/showers
1 per 40 pupils or part thereof
-
-
1 per 8 pupils or part thereof
1 per 6 pupils or part thereof
Sl. No
Fixtures
Nursery School
Public Rooms
Public Rooms
Non-Residential staff
Non-Residential staff
(1)
(2)
Table 5.19Sanitation Requirements for Hostels (Ref. NBC 2016 Part 9, Section 2, Clause 4.2.5.1, Table 12)
Sl. No.
Fixtures
Resident
Non-Resident
Visitors/CommonRooms
Males
Females
Males
Females
Males
Females
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
i)
Water Closets
1 per 8 or part thereof
1 per 6 or part thereof
1 for up to 15 2 for 16 to 35 3 for 36 to 65 4 for 66 to100
1 for up to 12 2 for 13 to 25 3 for 26 to 40 4 for 41 to 57 5 for 58 to 77 6 for 78 to 100
1 per 100 Up to 400 Over 400 add at 1 per250
2 per 100 Up to 200 Over 200 add at 1 per100
ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 Water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iii)
Urinals
1 per 25 or part thereof
-
Nil up to 6 1 for 7 to 20 2 for 21 to 45 3 for 46 to 70 4 for 71 to100
-
1 per 50 or part thereof
iv)
Wash basins
1 per 8 persons or part thereof
1 per 6 persons or part thereof
1 for up to 15 2 for 16 to 35 3 for 36 to 65 4 for 66 to100
1 for up to 12 2 for 13 to 25 3 for 26 to 40 4 for 41 to 57 5 for 58 to 77 6 for 78 to 100
1 per WC/Urinal
1 per WC
v)
Bath/showers
1 per 8 persons or part thereof
1 per 6 persons or part thereof
-
-
-
-
vi)
Cleaner's sink
------------------------------------1 per each floor --------------------------------------------
NOTE- Some WCs may be Indian style, if desired.
Table 5.20Sanitation Requirements for Fruit and Vegetable Markets (Ref. NBC 2016 Part 9, Section 2, Clause 4.2.5.1, Table 13)
Sl. No.
Fixtures
Shop Owners
Common Toilets Market Building
Public Toilet for Floating Population
Males
Females
Males
Females
Males
Females
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
i)
Water Closets
1 per 8 or part thereof
1 for up to 15 2 for 16 to 35 3 for 36 to 65 4 for 66 to100
1 for up to 12 2 for 13 to 25 3 for 26 to 40 4 for 41 to 57 5 for 58 to 77 6 for 78 to 100
1 per 50 (Min 2) Over 400 add at 1 per 250
1 per 50 (Min 2) Over 200 add at 1 per100
ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 Water tap with draining arrangements shall be provided in receiving/ sale area of each shop and for every 50 persons or part thereof in the vicinity of water closets and urinals
iii)
Urinals
-
-
Nil up to 6 1 for 7 to 20 2 for 21 to 45 3 for 46 to 70 4 for 71 to100
-
1 per 50
-
iv)
Wash basins
1 per 8 or part thereof
1 for up to 15 2 for 16 to 35 3 for 36 to 65 4 for 66 to100
1 for up to 12 2 for 13 to 25 3 for 26 to 40 4 for 41 to 57
-
-
v)
Bath/showers
1 per 8 persons or part thereof
1 per 6 persons or part thereof
-
-
1 per 50 persons
1 per 50 persons
NOTE-1) Toilet facilities for individual buildings in a market should be taken same as that for office buildings. 2) Common toilets in the market buildings provide facilities for persons working in shops and their regular visitors. 3) Special toilet facilities for a large floating population of out of town buyers/sellers, labourers, drivers of vehicles for whom special toilet (public toilets).
Table 5.21Sanitation Requirements for Bus Stations, Airports and Railway Stations (Ref. NBC 2016 Part 9, Section 2, Clause 4.2.5.1, Table 14)
Sl. No.
Fixtures
Junction Stations, Intermediate Stations and Bus Stations
Terminal Railway and Bus Stations
Domestic and International Airports
Males
Females
Males
Females
Males
Females
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
i)
Water Closets
3 for up to 1000 Add 1 per additional 1000 or part thereof
4 for up to 1000 Add 1 per additiona l 1000 or part thereof
4 for up to 1000 Add 1 per additional 1000 or part thereof
5 for up to 1000 Add 1 per additional 1000 or part thereof
For 200: 5 For 400: 9 For 600: 12 For 800: 16 For 1000: 18
For 200: 8 For 400: 15 For 600: 20 For 800: 26 For 1000: 29
Sl. No.
Fixtures
Junction Stations, Intermediate Stations and Bus Stations
Terminal Railway and Bus Stations
Domestic and International Airports
Males
Females
Males
Females
Males
Females
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 Water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iii)
Urinals
4 for up to1000Add 1 per additional1000
-
6 for up to1000Add 1 per additional1000
-
1 per 40 or part thereof
-
iv)
Wash basins
1 per WC/Urinal
1 per WC
1 per WC/Urinal
1 per WC
1 per WC/Urinal
1 per WC
v)
Bath/showers
2 per 1000
3 per 1000
4 per 1000
vi)
Drinking water fountain or taps (in common lobby for male/female)
2 per 1000 or part thereof
3 per 1000 or part thereof
4 per 1000 or part thereof
vii)
Cleaner's sink
1 per toilet compartme nt with 3 WCs
1 per toilet compart ment with 3 WCs
1 per toilet compartme nt with 3 WCs
1 per toilet compar tment with 3 WCs
1 per toilet compartment with 3 WCs
1 per toilet compartment with 3 WCs
NOTE-1) Some WCs may be Indian style, if desired. 2) Male population may be assumed as three-fifth and female populations two-fifth 3) Separate provision shall be made for staff and workers.
Table 5.22Sanitation Requirements for Shopping Mall and Retail Buildings (Ref. NBC 2016 Part 9, Section 2, Clause 4.2.5.1, Table 15)
Sl. No
Fixtures
Staff Toilets in Shopping Building
Staff Toilets in Shopping Building
Public Toilet for Floating Population
Public Toilet for Floating Population
(1)
(2)
Males
Females
Males
Females
(1)
(2)
(5)
(6)
(7)
(8)
i.
Water closets
1 for up to 15 2 for 16 to 35 3 for 36 to 65 4 for 66 to 100
1 for up to 12 2 for 13 to 25 3 for 26 to 40 4 for 41 to 57 5 for 58 to 77 6 for 78 to 100
1 per 50 (Min 2)
1 per 50 (Min 2)
ii.
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
iii.
Urinals
Nil up to 6 1 for 7 to 20 2 for 21 to 45 3 for 46 to 70 4 for 71 to 100
-
1 per 50
-
Sl. No
Fixtures
Staff Toilets in Shopping Building
Staff Toilets in Shopping Building
Public Toilet for Floating Population
Public Toilet for Floating Population
(1)
(2)
Males
Females
Males
Females
(1)
(2)
(5)
(6)
(7)
(8)
iv.
Wash basins
1 for up to 15 2 for 16 to 35 3 for 36 to 65 4 for 66 to 100
1 for up to 12 2 for 13 to 25 3 for 26 to 40 4 for 41 to 57
1 per 50 (Min 2)
1 per 50 (Min 2)
v.
Bath/showers
1 per 100 persons
1 per 100 persons
-
-
NOTES: (1) Toilet facilities for individual facilities in a shopping building should be taken same as that for office buildings. (2) Staff toilets in the shopping buildings provide facilities for persons working in shops and buildings, as well as for maintenance staff. (3) The number of persons against the fixture bath/showers represents the maintenance staff requiring such facility. (4) Public toilet facilities are provided for a large floating population for buyers and visitors.
NOTES: (1) Toilet facilities for individual facilities in a shopping building should be taken same as that for office buildings. (2) Staff toilets in the shopping buildings provide facilities for persons working in shops and buildings, as well as for maintenance staff. (3) The number of persons against the fixture bath/showers represents the maintenance staff requiring such facility. (4) Public toilet facilities are provided for a large floating population for buyers and visitors.
5.3.2.4Construction Site
(1). At construction sites, one toilet must be provided per 20 employees. In a work zone with between 21 and 199 employees, a toilet seat and one urinal must be provided for every 40 employees. For 200 or more workers, regulations call for a toilet seat and a urinal per 50 workers. The toilet must be located within 200 m or 5-minute walk.
(2). Job sites that are not equipped with a sanitary sewer must, unless prohibited by local codes, provide privies, in locations where their use will not contaminate either ground or surface water. Other alternatives to a privy could be chemical toilets, re-circulating toilets, or combustion toilets.
(3). Toilets should be cleaned regularly and maintained in good order, running water, must be provided along with soap and individual hand towels.
5.3.2.5 Temporary Camp Toilets.- Toilet facilities shall be provided within 60 m of the, site, which shall not be closer than 15 m of dining area or kitchen. Make sure that toilet area is cleaned at least once per day, it is sanitary, adequately lighted and is employee safe.
5.3.2.6Special / Contingency Toilets
(1) For Special events like open air theatre, religious/political gatherings, mela, etc. for which there are no permanent toilet facilities, contingency toilets/PSUs shall be provided. The following considerations shall determine the number of toilets to be provided for particular event:
(a) Duration of the event;
(b) Type of crowd;
(c) Weather conditions; and
(d) Whether finishing times are staggered if the event has multi-functions and the following guidelines shall be applied with minimum 50 per cent female toilets.
Table 5.23Contingency Toilets facilities for Special Events
Sl.No.
Patrons
For Males
For Females
Toilets
Urinals
Sinks
Toilets
Sinks
1
<500
1
2
2
6
2
2
<1000
2
4
4
9
4
3
<2000
4
8
6
12
6
4
<3000
6
15
10
18
10
5
<5000
8
25
17
30
17
(3) Special Purpose Toilets: Special toilet facilities shall be adequately provided in public projects (transport terminals/ healthcare and other public spaces) in million plus cities for the Third gender with appropriate cleanliness arrangements.
5.1.6 Mezzanine Floor
5.1.6.1 Height.- It shall have a minimum height of 2.2m.
5.1.6.2 Size.- The minimum size of the mezzanine floor, if it is to be used as a living room, shall not be less than 9.5Sq.m. The aggregate area of such mezzanine floor in a building shall in no case exceed one third the plinth area of the building.
5.1.6.3 Other Requirements.- A mezzanine floor may be permitted over a room or a compartment provided:
(a) it conforms to the standard of living rooms as regards lighting and ventilation in case the size of mezzanine floor is 9.5Sq.m or more
(b) It is so constructed as not to interfere under any circumstances with the ventilation of the space over and under it;
(c) Such mezzanine floor is not sub-divided into smaller compartments;
(d) ) Such mezzanine floor or any part of it shall not be used as a kitchen; and
(e) In no case shall a mezzanine floor be closed so as to make it liable to be converted into unventilated compartments.
5.1.7 Store Room
5.1.7.1 Height.- The height of a store room shall be not less than 2.1m.
5.1.7.2 Size.- The size of a store room, where provided in a residential building, shall be not less than 3 Sq.m
5.1.8 Garage
5.1.8.1 Height.- The height of a garage shall be not less than 2.4m.
5.1.8.2 Size.- The size of garages shall be as below:
(a) Private Garage - 3.0 m × 6.0 m, minimum; and
(b) Public Garage - Based on the number of vehicles parked by ECS
(b) In the case of a corner plot, the boundary wall shall be constructed as specified by the ULB or the Government. and
(c) However, the provisions of (a) and (b) are not applicable to boundary walls of jails. In electric sub-stations, transformer stations, institutional buildings like sanatoria, hospitals, industrial buildings like workshops, factories and educational buildings like schools, colleges, including hostels and other uses of public utility undertakings and strategically sensitive buildings, a height up to 2.4 m may be permitted by the Authority.
5.1.13 Septic Tanks.- Where a septic tank is used for sewage disposal, the location, design and construction of septic tank shall conform to requirements as notified by the Government.
5.1.14 Office-cum-Letter Box Room.- In the case of multi-storeyed multi-family dwelling apartments constructed by existing and proposed Apartment Owners Associations, limited companies and proposed societies, an office-cum-letter box room of 10Sq.m shall be provided on the ground floor. In case the number of flats is more than 20, the minimum size of the office-cum-letter box room shall be 20Sq.m and shall not exceed 40Sq.m. If the area of the office-cum-letter box room exceeds 40Sq.m, the additional area shall be considered for FAR calculation.
In case of Business buildings provisions shall be made for letter boxes on the entrance floor as per the requirements of the postal department.
5.1.15 Meter Rooms.- For all buildings above 15m in height and in special occupancies, like educational, assembly, institutional, industrial, storage, hazardous and mixed occupancies with any of the aforesaid occupancies having area more than 500m2 on each floor, provision shall be made for an independent and ventilated meter (service) room, as per requirements of electric (service) supply undertakings on the ground floor with direct access from outside for the purpose of termination of electric supply from the licensee’s service and alternative supply cables. The door/doors provided for the service room shall have fire resistance of not less than two hours.
NOTE: Staff and public toilet utilities are generally common in office buildings. Where public toilets are to be provided independently, similar requirements as that of staff toilet may be provided.
NOTE: Staff and public toilet utilities are generally common in office buildings. Where public toilets are to be provided independently, similar requirements as that of staff toilet may be provided.
NOTE: Staff and public toilet utilities are generally common in office buildings. Where public toilets are to be provided independently, similar requirements as that of staff toilet may be provided.
NOTE: Staff and public toilet utilities are generally common in office buildings. Where public toilets are to be provided independently, similar requirements as that of staff toilet may be provided.
NOTE: Staff and public toilet utilities are generally common in office buildings. Where public toilets are to be provided independently, similar requirements as that of staff toilet may be provided.
-
add @ 2.5%
-
iv)
Wash basins Wash basins in rows or troughs and taps spaced 750 mm c/c
1 per 25 or part thereof
1 per 25 or part thereof
1 per 25 or part thereof
1 per 25 or part thereof
v)
Drinking water fountain
1 per every 100 or part thereof with minimum one on each floor
1 per every 100 or part thereof with minimum one on each floor
1 per every 100 or part thereof with minimum one on each floor
1 per every 100 or part thereof with minimum one on each floor
vi)
Cleaner's sink
1 on each floor
1 on each floor
1 on each floor
1 on each floor
vii)
Showers / bathing rooms
1 in each water closet
1 in each water closet
1 in each water closet
1 in each water closet
Sl. No.
Fixtures
Offices / Visitors
Offices / Visitors
Workers
Workers
Sl. No.
Fixtures
Males
Females
Males
Females
(1)
(2)
(3)
(4)
(5)
(6)
viii)
Emergency shower and eye wash fountain
-
-
1 per every shop floor per 500 persons
1 per every shop floor per 500 persons
NOTES: 1. For factories requiring workers to be engaged in dirty and dangerous operations or requiring them to being extremely clean and sanitized conditions additional and separate (if required so) toilet facilities and if required by applicable Industrial and safety laws and the Factories Act shall be provided in consultation with the user. 2. Depending on the type of disability of a person and the hazard posed by the type of activities in the factory for a person with disabilities, if a person with disabilities is decided to be engaged for a particular activity, the requirements of accessibility shall be guided by the provisions given in 13 of Part 3 'Development Control Rules and General Building Requirements' of the Code.
NOTES: 1. For factories requiring workers to be engaged in dirty and dangerous operations or requiring them to being extremely clean and sanitized conditions additional and separate (if required so) toilet facilities and if required by applicable Industrial and safety laws and the Factories Act shall be provided in consultation with the user. 2. Depending on the type of disability of a person and the hazard posed by the type of activities in the factory for a person with disabilities, if a person with disabilities is decided to be engaged for a particular activity, the requirements of accessibility shall be guided by the provisions given in 13 of Part 3 'Development Control Rules and General Building Requirements' of the Code.
NOTES: 1. For factories requiring workers to be engaged in dirty and dangerous operations or requiring them to being extremely clean and sanitized conditions additional and separate (if required so) toilet facilities and if required by applicable Industrial and safety laws and the Factories Act shall be provided in consultation with the user. 2. Depending on the type of disability of a person and the hazard posed by the type of activities in the factory for a person with disabilities, if a person with disabilities is decided to be engaged for a particular activity, the requirements of accessibility shall be guided by the provisions given in 13 of Part 3 'Development Control Rules and General Building Requirements' of the Code.
NOTES: 1. For factories requiring workers to be engaged in dirty and dangerous operations or requiring them to being extremely clean and sanitized conditions additional and separate (if required so) toilet facilities and if required by applicable Industrial and safety laws and the Factories Act shall be provided in consultation with the user. 2. Depending on the type of disability of a person and the hazard posed by the type of activities in the factory for a person with disabilities, if a person with disabilities is decided to be engaged for a particular activity, the requirements of accessibility shall be guided by the provisions given in 13 of Part 3 'Development Control Rules and General Building Requirements' of the Code.
NOTES: 1. For factories requiring workers to be engaged in dirty and dangerous operations or requiring them to being extremely clean and sanitized conditions additional and separate (if required so) toilet facilities and if required by applicable Industrial and safety laws and the Factories Act shall be provided in consultation with the user. 2. Depending on the type of disability of a person and the hazard posed by the type of activities in the factory for a person with disabilities, if a person with disabilities is decided to be engaged for a particular activity, the requirements of accessibility shall be guided by the provisions given in 13 of Part 3 'Development Control Rules and General Building Requirements' of the Code.
NOTES: 1. For factories requiring workers to be engaged in dirty and dangerous operations or requiring them to being extremely clean and sanitized conditions additional and separate (if required so) toilet facilities and if required by applicable Industrial and safety laws and the Factories Act shall be provided in consultation with the user. 2. Depending on the type of disability of a person and the hazard posed by the type of activities in the factory for a person with disabilities, if a person with disabilities is decided to be engaged for a particular activity, the requirements of accessibility shall be guided by the provisions given in 13 of Part 3 'Development Control Rules and General Building Requirements' of the Code.
←——— 1 per 100 persons or part thereof →
←——— 1 per 100 persons or part thereof →
←——— 1 per 100 persons or part thereof →
←——— 1 per 100 persons or part thereof →
vi)
Cleaner's sink
←——— 1 per floor (Minimum) →
←——— 1 per floor (Minimum) →
←——— 1 per floor (Minimum) →
←——— 1 per floor (Minimum) →
vii)
Showers/ bathing rooms
←——— As per requirements →
←——— As per requirements →
←——— As per requirements →
←——— As per requirements →
NOTES:1. Some WCs may be Indian style, if desired.2. Male population may be assumed as two-third and female populations as one-third.
NOTES:1. Some WCs may be Indian style, if desired.2. Male population may be assumed as two-third and female populations as one-third.
NOTES:1. Some WCs may be Indian style, if desired.2. Male population may be assumed as two-third and female populations as one-third.
NOTES:1. Some WCs may be Indian style, if desired.2. Male population may be assumed as two-third and female populations as one-third.
NOTES:1. Some WCs may be Indian style, if desired.2. Male population may be assumed as two-third and female populations as one-third.
NOTES:1. Some WCs may be Indian style, if desired.2. Male population may be assumed as two-third and female populations as one-third.
(3)
Boys
Girls
Boys
Girls
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(vi)
Drinking water fountain or taps
1 per 50 pupils or part thereof
1 per 50 pupils or part thereof
1 per 50 pupils or part thereof
1 per 50 pupils or part thereof
1 per 50 pupils or part thereof
(vii)
Cleaner's sink
1 per each floor
1 per each floor
1 per each floor
1 per each floor
1 per each floor
NOTES: (1) Some WCs may be Indian style, if desired (2) For teaching staff, the schedule of fixtures to be provided shall be the same as in case of office building.
NOTES: (1) Some WCs may be Indian style, if desired (2) For teaching staff, the schedule of fixtures to be provided shall be the same as in case of office building.
NOTES: (1) Some WCs may be Indian style, if desired (2) For teaching staff, the schedule of fixtures to be provided shall be the same as in case of office building.
NOTES: (1) Some WCs may be Indian style, if desired (2) For teaching staff, the schedule of fixtures to be provided shall be the same as in case of office building.
NOTES: (1) Some WCs may be Indian style, if desired (2) For teaching staff, the schedule of fixtures to be provided shall be the same as in case of office building.
NOTES: (1) Some WCs may be Indian style, if desired (2) For teaching staff, the schedule of fixtures to be provided shall be the same as in case of office building.
NOTES: (1) Some WCs may be Indian style, if desired (2) For teaching staff, the schedule of fixtures to be provided shall be the same as in case of office building.
NOTES: (1) Toilet facilities for individual facilities in a shopping building should be taken same as that for office buildings. (2) Staff toilets in the shopping buildings provide facilities for persons working in shops and buildings, as well as for maintenance staff. (3) The number of persons against the fixture bath/showers represents the maintenance staff requiring such facility. (4) Public toilet facilities are provided for a large floating population for buyers and visitors.
NOTES: (1) Toilet facilities for individual facilities in a shopping building should be taken same as that for office buildings. (2) Staff toilets in the shopping buildings provide facilities for persons working in shops and buildings, as well as for maintenance staff. (3) The number of persons against the fixture bath/showers represents the maintenance staff requiring such facility. (4) Public toilet facilities are provided for a large floating population for buyers and visitors.
NOTES: (1) Toilet facilities for individual facilities in a shopping building should be taken same as that for office buildings. (2) Staff toilets in the shopping buildings provide facilities for persons working in shops and buildings, as well as for maintenance staff. (3) The number of persons against the fixture bath/showers represents the maintenance staff requiring such facility. (4) Public toilet facilities are provided for a large floating population for buyers and visitors.
NOTES: (1) Toilet facilities for individual facilities in a shopping building should be taken same as that for office buildings. (2) Staff toilets in the shopping buildings provide facilities for persons working in shops and buildings, as well as for maintenance staff. (3) The number of persons against the fixture bath/showers represents the maintenance staff requiring such facility. (4) Public toilet facilities are provided for a large floating population for buyers and visitors.