12.1 Scope.-This part covers the requirements of the fire protection for the multi-storeyed buildings (high rise buildings) and the buildings, which are of 15m and above in height and low occupancies of categories such as Assembly, Institutional, Educational (more than two storeyed and built-up area exceeds 1000Sq.m), Business (where plot area exceeds 500Sq.m), Mercantile (where aggregate covered area exceeds 750Sq.m), Hotel, Hospital, Nursing Homes, Underground Complexes, Industrial Storage, Meeting/Banquet Halls, Hazardous Occupancies.
12.2 Procedure for obtaining NOC and Clearance Certificate from DFES.- The procedure of obtaining NOC from Department of Fire and Emergency Services (DFES) is detailed in clause no. 3.10.5 and the procedure of obtaining Clearance Certificate is detailed in Clause no. 3.17
12.3 Renewal of fire clearance.- On the basis of undertaking given by the Applicant and the professional on record, the Chief Fire Officer shall renew the fire clearance in respect of all High-Rise buildings on annual Basis
12.4 Fee.- For augmentation of fire service facilities for effecting rescue/fire fighting operation in high rise building, fee payable to Chief Fire Officer by the applicant(s) along with sets of plans for obtaining the No Objection Certificate shall be as notified by the Government.
12.5 Responsibility of providing Fire Protection and Fire Fighting Measures.- The engaged Competent Professional on record for preparation of plans for NOC and the professional on record for supervising the works (as per Appendix-I) of the project shall be responsible for making provisions for fire protection and fire fighting measure as provided in this Chapter.
12.6 Terminology.- For the purpose of this Chapter all the technical terms shall have the meaning as defined in National Building Code of India, Part-IV, Fire Protection as amended from time to time but for the terms which are defined otherwise in these bye-Laws.
12.7 General .- The DFES may insist on suitable provisions in the buildings from fire safety and means of escape point of view depending on the occupancy, height or on account of new developments creating special fire hazard, in addition to the provision of these building bye laws and part IV (Fire Protection) of National Building Code of India, which are not contradicting to the provision of the Zonal Regulations.
12.7.1 Fire Resistance of Types of Constructions / Building Components.- The fire resistance ratings for various types of construction for structural and non-structural members shall be as given in Table 1 of Part-4 of the NBC, 2005.Building elements/components such as walls, columns, beams and floors shall have the requisite fire resistance rating in accordance with the accepted standards as specified in Part-4 of the NBC 2016.
12.7.2 Means of Access .- As provided in Zonal Regulations.
12.7.3 Provisions of Exterior Open Spaces around the building.- As provided in Zonal Regulations
12.7.4 Exit Requirement
As provided in Section 4.2 of Part 4, NBC 2016
As provided in Section 4.2 of Part 4, NBC 2016
Type of Exits: As provided in Section 4.2 of Part 4, NBC 2016
Number of Size of Exits: As provided in Section 4.4.2.1 of Part 4, NBC 2016.
Arrangements of Exits: As provided in Section4.4.2.2 of Part 4, NBC 2016
Occupant Load: As provided in Section 4.3 of Part 4, NBC 2016.
Capacity of Exit: As provided in Section4.4.2.3 of Part 4, NBC 2016
Staircase Requirements: As provided in Section 4.4.2.4.3 of Part 4, NBC 2016.
Minimum Width Provision for Stairways: As provided in Section 4.4.2.4.3.2 of Part 4, NBC 2016
Minimum Width Provision for Passageway/Corridors: As provided in Section 4.4.2.4.2 of Part 4, NBC 2016
Doorways: As provided in Section 4.4.2.4.1of Part 4, NBC 2016
Stairways: As provided in Section 4.4.2.4.3.2 of Part 4, NBC 2016
12.8 Fire Escapes or External Stairs:
(1) Fire escape including Occupant load and Travel distance shall not be taken into account while calculating the number of staircases for a building.
(2) All fire escapes shall be directly connected to the ground.
(3) Entrance to the fire escape shall be separate and remote from internal staircase.
(4) The route to fire escape shall be free of obstructions at all times except the doorway leading to the fire escape which shall have the required fire resistance.
(5) Fire escape shall be constructed of non-combustible materials.
(6) Fire escape stairs shall have straight flight not less than 125cm wide with 25cm treads and risers not more than 19cm.
(7) Handrails shall be at a height not less than 100cm.
(8) Fire escape staircase in the mercantile, business, assembly, hotel buildings above 24m height shall be a fire tower and in such a case width of the same shall not be less than the width of the main staircase. No combustible material shall be allowed in the fire tower.
12.8.1 Spiral Stairs
(1) The use of spiral staircase shall be limited to low occupant load and to building height of 9m.; and
(2) A spiral stair shall not be less than 150cm in diameter and shall be designed to give the adequate headroom.